Data Center: Cabinet Technical Specifications
Body
| |
ITC Data Center
|
|
Type of Racks
|
• Chatsworth Terra-Frame
• Vertical rails
• Peg and post mounting.
|
|
Capacity
|
• Generally 20 power connections per rack but higher options may be available with different cooling approaches
|
|
Power & Cooling
|
• 120V or 208V
• Triple phase
• 20 AMP (30AMP may be available)
• Maximum draw of approximately
• Chimney cooling on racks
• Optional back door cooling may be purchased to increase capacity
• Capacity is approximately 4 KW per rack with chimney cooling
• Capacity 12 KW per rack with back door cooling
|
|
Network
|
• One network connection will be provided for each device installed within the rack.
• ITS will provide 1Gb connections through a top of rack switch.
|
|
Weight
|
• The total weight of a full rack cannot exceed 3000 lbs.
|