Data Center: Cabinet Technical Specifications

Body

 

ITC Data Center

Type of Racks

• Chatsworth Terra-Frame

• Vertical rails

• Peg and post mounting.

Capacity

• Generally 20 power connections per rack but higher options may be available with different cooling approaches

Power & Cooling

• 120V or 208V

• Triple phase

• 20 AMP (30AMP may be available)

• Maximum draw of approximately

• Chimney cooling on racks

• Optional back door cooling may be purchased to increase capacity

• Capacity is approximately 4 KW per rack with chimney cooling

• Capacity 12 KW per rack with back door cooling

Network

• One network connection will be provided for each device installed within the rack.

• ITS will provide 1Gb connections through a top of rack switch.

Weight

• The total weight of a full rack cannot exceed 3000 lbs.